Performance Data
|
| All Models Listed To UL2200 Standard - |
| Standby Ouput (KW): 200 |
| Prime Output (KW): 180 |
| Design: Revolving field. Self-ventilated. Drip-proof. Single Bearing. Synchronous |
| No. of Poles: 4 Pole |
| Excitation: Permanent Magnet Generator (PMG) Excitation |
| Generator RPM: 1800 |
| Votage - 3 Phase: 120/208V, 120/240V, 277/480V |
| Voltage - Single Phase: 120/240V |
| Voltage Selector Switch: Consult Factory |
| Armature Connection: 12-Lead Reconnectable |
| Amps - Three Phase 208V: 694 |
| Amps - Three Phase 240V: 601 |
| Amps - Three Phase 480V: 301 |
| Amps - Single Phase 240V: 633 |
| Voltage Regulation - (No load to Full load): 1% |
| Power Factor: 0.80 |
| Frequency: 60 Hz* |
| *(50 hz models availble on request) |
| Insulation: Class H |
| |
Power Source
|
| Engine Make/Model: Volvo TWD740GE |
| Starting System: 24VDC |
| Design: 4 Cycle Turbocharged Water to Air Intercooled |
| Displacement: 7.28 liter |
| No. Cylinders: 6 In-line |
| Bore x Stroke In.(mm): 4.21 x 5.31(107 x 135) |
| HP at Rated Speed: 310 |
| Fuel Tank Capacity Gal.: Optional |
| Fuel Consumption @ Standby Rating: |
| Full load gph: 14.7 |
| 3/4 load gph: 11.1 |
| 1/2 load gph: 7.4 |
| 1/4 load gph: 3.7 |
| Engine Coolant Capacity gal.: 4.23 |
| Oil Capacity with filters gal.: 7.7 |
| Battery: 2 x 143 AH |
| |
Dimensions
|
| Overal Length - Open (Housed) in. : 108.70 in. (115 in.) |
| Overal Width - Open (Housed) in. : 53 in. (57 in.) |
| Overal Height - Open (Housed) in. : 58.77 in. (74 in.) |
| Approx. Weight - Dry: 4,033 lbs. |
| Approx. Weight - Wet: 4,172 lbs. |
| |